yum install usbutils apcupsd
(pakiet apcupsd-cgi - nie jest nam potrzebny do interfejsu webowego)
lsusb
Bus 001 Device 003: ID 0d9f:0004 Powercom Co., Ltd
vim /etc/apcupsd/apcupsd.conf
## apcupsd.conf v1.1 ## UPSNAME Powercom UPSCABLE usb UPSTYPE usb DEVICE LOCKFILE /var/lock SCRIPTDIR /etc/apcupsd PWRFAILDIR /etc/apcupsd NOLOGINDIR /etc ONBATTERYDELAY 6 BATTERYLEVEL 5 MINUTES 3 TIMEOUT 0 ANNOY 300 ANNOYDELAY 60 NOLOGON disable KILLDELAY 0 NETSERVER on NISIP 0.0.0.0 NISPORT 3551 EVENTSFILE /var/log/apcupsd.events EVENTSFILEMAX 10 UPSCLASS standalone UPSMODE disable STATTIME 0 STATFILE /var/log/apcupsd.status LOGSTATS off DATATIME 0
service apcupsd start
chkconfig apcupsd on
apcaccess status
APC : 001,036,0834 DATE : 2017-03-15 12:47:43 +0200 HOSTNAME : KVM1 VERSION : 3.14.12 (29 March 2014) redhat UPSNAME : Powercom CABLE : USB Cable DRIVER : USB UPS Driver UPSMODE : Stand Alone STARTTIME: 2017-03-15 12:44:12 +0200 MODEL : HID UPS Battery STATUS : ONLINE LINEV : 220.0 Volts LOADPCT : 0.0 Percent BCHARGE : 96.0 Percent TIMELEFT : 409.6 Minutes MBATTCHG : 5 Percent MINTIMEL : 3 Minutes MAXTIME : 0 Seconds OUTPUTV : 220.0 Volts DWAKE : 0 Seconds ITEMP : -273.1 C ALARMDEL : No alarm BATTV : 220.0 Volts LINEFREQ : 50.0 Hz NUMXFERS : 0 TONBATT : 0 Seconds CUMONBATT: 0 Seconds XOFFBATT : N/A SELFTEST : OK STATFLAG : 0x05000008 MANDATE : 2009-12-23 SERIALNO : 004-0D9F-000 BATTDATE : 2009-12-23 NOMOUTV : 220 Volts NOMINV : 220 Volts NOMBATTV : 220.0 Volts END APC : 2017-03-15 12:47:43 +0200
vim /etc/zabbix/zabbix_agentd.d/ups.conf
UserParameter=ups.status,apcaccess -p STATUS
UserParameter=ups.charge,apcaccess -p BCHARGE | awk -F "." '{print $1}'
UserParameter=ups.volts,apcaccess -p LINEV | awk -F "." '{print $1}'
Na serwerze tworzymy 3 elementy (items):
ups.charge, ups.status, ups.volts
dla ups.status ustawiamy trigger:

Dla pozostałych tworzymy wykres: